NORSEMAN™ WOOD SOLID WARM AIR FURNACE
Model 2500 and 1500 Owners Manual

(Save this manual for future reference. Go to PDF format for printing.)

READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING
THIS FURNACE.
Failure to follow instructions
may result in property damage, bodily injury, or even death.

NOTE: Installation MUST be
completed by a qualified
Heating Equipment Installer!


May NOT be installed in mobile homes, manufactured homes, trailers or tents.
(No Exceptions)

This furnace meets
U.S. Test Standard:

UL 391

SAFETY INSTRUCTIONS

Warnock Hersey
Safety Notice: If this furnace is NOT properly installed, a house/building fire may result. For your safety, contact local building or fire officials about permits, restrictions, and installation requirements for your area.

READ ALL INSTRUCTIONS CAREFULLY.
Refer to instruction panels, caution and warning plates on furnace for additional information.

  1. This furnace is designed for INDOOR INSTALLATION ONLY.
  2. DO NOT attempt to retrofit this unit with any type of water coil or water jacket.
  3. The installation of this furnace must comply with your local building code rulings. Please observe the clearances to combustibles (see figure 1, figure 2, figure 3). Do not place furniture or other objects within the clearance area.
  4. Verify that the furnace is properly installed before
    firing for the first time. Obtain the services of a professional licensed installer familiar with all aspects of safe and correct installation. DO NOT use temporary or makeshift compromises during installation.
  5. DO NOT store wood, flammable liquids or other combustible materials too close to the unit. Refer to the certification label on back of unit and reference
    clearance instructions in this manual.
  6. Do not install this furnace in a mobile home, manufactured home, tent or trailer – NO EXCEPTIONS! (HUD Federal Standard: 24 CFR Ch.XX)
  7. If any parts are missing or defective, please notify the manufacturer or dealer immediately. DO NOT OPERATE A STOVE THAT IS MISSING ANY PARTS.
  8. Always connect this furnace to a chimney and vent to the outside. Never vent to another room or inside a building. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
  9. DO NOT CONNECT to an aluminum Type B gas vent. This is not safe. Use approved masonry or a UL 103 HT Listed Residential Type and Building Heating Appliance Chimney. Use a 6" diameter chimney or larger, that is high enough to provide required draft (see specifics in installation instructions.)
  10. Inspect flue pipes, pipe joints, and flue pipe seals regularly to ensure that smoke and flue gases are not drawn into, and circulated by the air circulation system.
  11. Cleaning of this furnace, is especially important at the end of the heating season. Accumulated ash attracts moisture and may cause corrosion during the summer months.
  12. Be sure that your chimney is safely constructed and in good repair. Have the chimney inspected by the fire department or a qualified inspector. Your insurance company may be able to recommend a qualified inspector.
  13. Creosote or soot may build up in the chimney connector and/or chimney and cause a house, building or chimney fire. Inspect the chimney connector and chimney twice monthly during the
    heating season and clean if necessary. (See Chimney Maintenance).
  14. To prevent injury, do not allow anyone to use this furnace who is unfamiliar with the correct operation of the furnace.
  15. Do not operate furnace while under the influence of drugs or alcohol.
  16. Ashes should not be allowed to accumulate higher than the ash pan. Dispose of ashes in a metal container with a tight fitting lid. Keep the closed container on a noncombustible floor or on the ground, well away from all combustible materials. Keep the ashes in the closed container until all cinders have thoroughly cooled. The ashes may be buried in the ground or picked up by a refuse collector.
  17. Build several small fires on first use. This will help to “season” the cast iron parts and avoid cracking. Allow furnace to cool between firings.
  18. The special paints used on your furnace may give off some smoke and an odor while they
    are curing during the first 12 to 15 fires.
    Additional smoke and odor may be emitted from the light oils used in construction of the fire box. This should disappear after a short period of time and not occur again. Persons with lung conditions or owners of susceptible domestic pets (such as birds) should take prudent precautions. Open windows
    and doors as needed to clear smoke and/or odor. Paint discoloration will occur if the furnace
    is over fired.
  19. This furnace has a painted surface which is durable but it will not stand rough handling or abuse. When installing your furnace, use care in handling. Clean with soap and warm water when furnace is not hot. Do not use any acids or scouring soap, as these solvents wear and dull the finish.
  20. While furnace is in operation, all persons, especially young children, should be alerted to the hazards from high surface temperatures and should be kept away to avoid burns or clothing ignition.
  21. If small children will be in the same room as the furnace during operation, provide a sturdy barrier to keep them at a safe distance from the stove. NEVER LEAVE SMALL CHILDREN UNSUPERVISED when they are in the same room as the stove.
  22. Keep furnace area clear and free from all combustible materials, gasoline, and other flammable vapors and liquids.
  23. To prevent burns, always wear protective clothing, leather hearth gloves and eye protection, while tending the fire.
  24. While in operation, keep the feed door, ash door, and cabinet door closed and secured at all times except while tending the fire.
  25. Do not overfire the furnace. Overfiring will occur if the feed door or ash door is left open during operation. Such actions can result in very dangerous operating conditions.
  26. For further information on using your furnace safely, obtain a copy of the National Fire Protection Association (NFPA) publication, "Using Coal and Wood Furnaces Safely" NFPA No. HS-10-1978. The address of the NFPA is: Battery March Park, Quincy, MA  02269.
NOTE:  INSTALLATION SHOULD BE COMPLETED BY A PROFESSIONAL, LICENSED HEATING AND COOLING CONTRACTOR ONLY.

FURNACE DESCRIPTION & INSTALLATION OPTIONS

Your NORSEMAN™ Solid Fuel Warm Air Furnace is designed to provide supplemental or central heating for your home. This solid fuel furnace may be installed in conjunction with a central furnace that is in proper operating condition and meets all national and/or local building codes, safety standards, required controls and has been installed in accordance with appropriate standards of the National Fire Protection Association and in accordance with the clearances specified on the furnace nameplate.

Installation of NORSEMAN™ Furnaces must be accomplished by a qualified heating contractor (one who is engaged in, and is responsible for, or is thoroughly familiar with the installation and operation of gas, oil, and solid fuel burning heating appliances, who is experienced in such work and familiar with all the requirements of the authority having jurisdiction.) The installation shall be in strict accordance with the manufacturer’s installation instructions furnished with the solid fuel furnace.

The chimney connector of the furnace is to be installed to provide clearances to combustible materials not less than specified in the individual classifications and marked on the furnace. The chimney must be suitable for use with residential type or building heating appliances which burn solid fuel.

The furnace is designed to operate in either parallel air flow arrangement with a central furnace or as a stand alone central furnace. (See connection option diagrams, figures 17 – 23 below)

Central Furnace Installation

As a central furnace, the unit functions independently of any other heating system. The blower(s) will come on when the plenum temperature reaches the setting on the blower control.

Parallel Installation

When the NORSEMAN™ Warm Air Furnace is installed in parallel with an existing central heating furnace, it is designed to turn on the central unit blower whenever the Warm Air Furnace blower turns on. The NORSEMAN™ blower will only come on when the temperature in the plenum has reached the setting on the blower control. This insures there will be sufficient warm air in the system to provide for efficient operation. When the central system thermostat calls for heat, the central system will operate by igniting the burner and turning on the blower. It is possible that both systems will operate simultaneously. For the most efficient use of your

NORSEMAN™ Warm Air Furnace, it is recommended that it be fired as much as possible in order to reduce the demand on the central heating system. An optional forced draft kit (Model DK-50) is available that operates from a wall thermostat. When the temperature falls below the setting on the wall thermostat, the forced draft will come on.

The warm air supply outlet of the NORSEMAN™ Furnace MUST NOT BE CONNECTED TO THE COLD AIR RETURN of the central heating furnace because of the possibility of overheating components of the central furnace and causing it to operate other than it was designed.

Operating external static pressure and air temperature rise of existing furnace must be within ratings marked on the central furnace nameplate. Test operation of central furnace after installation of supplementary furnace.


Locating Furnace

NOTICE: Installation of this furnace must be done by a qualified heating equipment installer.

CAUTION: FURNACE UNITS ARE HEAVY.

UNITS WEIGH APPROXIMATELY 450-550 LBS. MAKE SURE YOU HAVE PROPER EQUIPMENT OR SUFFICIENT MANPOWER TO PREVENT INJURY WHEN DELIVERING AND LOCATING FURNACE UNITS.


CAUTION:  DO NOT OPERATE THIS APPLIANCE WITH CRACKED OR MISSING FIREBRICKS.

  1. The furnace must be placed on solid concrete or masonry floor. NOTE: To reduce weight during installation remove parts from inside the firebox. Additional weight reductions can be obtained by removing the fire brick. Make note of position so they are returned to the same positions.
  2. The furnace should be located in the same room as the central heating system, as close as possible but no closer than 6˝ to the central system. (See figures 16 – 23 below)
  3. Observe the clearances to combustible materials (see figure 1, figure 2 and figure 3).
  4. The furnace must have its own flue. Do not connect this unit to a chimney flue serving other appliances.
  5. Install furnace pipe, elbows, and thimble as required, utilizing either a recently cleaned and inspected 6" masonry chimney or a 6" i.d. listed UL 103 HT chimney. NOTE: A barometric draft regulator may be necessary if the chimney draft is found to be excessive.
  1. Use 6" round black furnace pipe, not
    galvanized furnace pipe. Secure pipe sections with three (3) sheet metal screws in each furnace pipe and/or elbow joint to firmly hold the pipe sections together.
  2. Recheck clearances from the furnace,
    connector furnace pipe, and corner clearances
    using the illustrations in figures 1 – 3 and your local building codes or fire protection ordinances.
    NOTE:  A studded wall faced with brick or stone should be considered a combustible surface.
  3. DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, MANUFACTURED HOME, TENT OR TRAILER. NO EXCEPTIONS! (HUD Federal Standard: 24 CFR Ch.XX)
  4. The clearances provided are minimum dimensions determined by the manufacturer’s testing facility in accordance with U.S. Test Standard UL 391. Installation of this furnace must comply with the latest edition of NFPA 211 for reduced clearances and/or your local building code rulings (use whichever minimum dimensions are LARGEST).

 

Minimum Clearances to Combustible Surfaces

Front: 48 in. Side: 16 in. Back: 26 in.
Chimney Connectors: 18 in.
Plenum to wall-studs, joists or finished wall or ceiling: 2 in.

 
Fig. 1 - TOP VIEW
Minimum Clearances from Combustible Surfaces
Fig. 2 - SIDE VIEW
Minimum Clearances from Combustible Surfaces

Fig. 3 - Minimum Plenum Clearances from Combustible Surfaces


Tools & Materials Required for Assembly and Installation

TOOLS REQUIRED MATERIALS REQUIRED
Safety Glasses
Gloves
Pencil
6 foot Tape Measure
Tin Snips
Sabre Saw
Drill

1/8" diameter Drill Bit (for sheet metal screws)

Screwdrivers (Phillips & Slotted)
6mm Socket with Driver
10mm Socket with Driver
10mm open end box wrench
7/16" box wrench
NOTE:  The following items are NOT  included with your furnace

Chimney Connection:
  6" black steel (24 ga. minimum) straight
  furnace pipe, elbow, Collar and Thimble
  (as required)
6" Barometric Draft Regulator (optional)
8" Round Butterfly Anti-Backdraft Damper
  (2 required - for parallel installation only)
Plenum & Duct Work (as required)
Chimney: Existing 6" Lined Masonry Chimney or
   6" Inside Diameter listed Type HT chimney.
1/2" Sheet Metal Screws
Electrical Wiring: 18 ga. AWG copper
   with 90° C min.
1/2" Conduit and Connectors
Furnace Cement (manufacturer recommends
   Rutland Code 78 or equivalent)


ASSEMBLY INSTRUCTIONS                              Refer to diagram and parts lists:  1500  |  2500
 
Your NORSEMAN™ Warm Air Furnace requires the following items to be assembled or installed by the furnace installer:
  Feed Door Pull Handle / Thermostat Assembly
  Feed Door Locking Handle
  Blower(s) and Blower Control
  Electrical Connections
  1. Remove all parts from inside the furnace and inspect for damage, including the firebrick as some breakage could occur during shipment. Do not operate furnace with broken or missing fire box bricks. Replace damaged bricks before operating furnace.
  2. Assemble the feed door handle a shown in
    figure 4. Install thermostat assembly and cover as shown.
  3. Align thermostat control know with flat on thermostat control shaft and press onto shaft (see figure 4).
  4. Attach feed door locking handle (see figure 5) with screw and nuts provided. NOTE: Slotted holes are for adjustment of handle. Adjust handle until pressure is required to lock feed door.
  5. Install Blower / Limit Control on rear of furnace cabinet using three (3) sheet metal screws (see figure 6).
  6. Remove blower(s) from carton(s). Attach the flexible conduit / wire assembly to the blower(s) before mounting.
  7. Remove junction box cover and take out the mounting hardware package. Position clip nuts to furnace housing around blower opening as shown in figure 6. [On Model #2500, install the right (when facing rear of furnace) blower first.] Install the blower(s) with gasket using 1/4-20 x 3/4" bolts.
  8. Secure the 4-inch square electrical junction box to the black bracket on the rear of the stove using two (2) sheet metal screws.
  9. Wire blower according to the wiring diagram shown (see figure 7 and figure 8). On model 2500, wire right side blower first (see figure 7). Replace junction box cover when complete.
  10. Connect operation of shaker grates with grate handle before loading fuel in furnace.

Fig. 4 Door / Handle / Thermostat Assembly

Fig. 5  Feed Door Handle Assembly

 

Fig. 6 Blower Assembly


Model 1500 has 1 blower centered on cabinet.
Model 2500 had 2 blowers - install right first.


Furnace Installation

NOTE: Installation must be made by a qualified heating equipment installer (one who is engaged in, and is responsible for, or is thoroughly familiar with the installation and operation of gas, oil, and solid fuel burning heating appliances, who is experienced in such work and familiar with all the building requirements and/or fire codes of the authority having local jurisdiction.)

This is a furnace, not a stove. Heated air must be directed away from the furnace or it will not operate properly.

  1. The installation is to be completed in accordance with National Fire Protection Association (NFPA) installation standards No. 89M, 90B, 211, 70 (National Electrical Code) and Uniform Mechanical Code 913, 6-4 in states where applicable (where code offers making flue pipe connections into an existing chimney with other fuel burning appliances).

  2. Wood /coal burning appliances need air for combustion and circulation to the house. Provision must be made to provide make up air so as not to starve the central heating system of combustion air. Have the local regulating authority determine that make up air supply is adequate. Reference NFPA standards No. 30 & 54, Code for Installation of Gas and Oil Equipment.

  3. Have the local regulating authority or qualified expert inspect all chimneys and installations for adequate venting and for compliance with standard local codes and regulations regarding installation of wood/coal burning appliances. (Also see Pipe Installation)

  4. Position the furnace according to clearances (see figure 1, figure 2, figure 3) and to maintain
    chimney connections as short as possible. Avoid unnecessary turns and installation of devices that would create excessive resistance to the flow of flue gases.

  5. Make flue pipe connections to the chimney with 24-gauge pipe and elbows (not included with furnace) maintaining proper clearances. Seal the flue pipe in the chimney with furnace cement. (Chimney connections must be securely supported and joints fastened with sheet metal screws or rivets.)

  6. For parallel installations, install (two) 8" anti-backdraft butterfly dampers (Vogelzang Model AD-8, not included with the furnace) in the heat (duct) pipes a minimum of 18 inches above the furnace plenum. Anti-backdraft butterfly dampers may be obtained where you purchased your appliance or from a local HVAC distributor.

  7. Install 8˝ diameter 26-gauge heat (duct) pipe and connectors (not included with furnace) to make connection to the plenum of the central heating system. The heat pipe, plenum, and connections must be constructed of metal with a minimum temperature rating of 250° F. If central air conditioning is installed in the plenum, install heat pipe above the air conditioning unit. Secure the heat pipe connection with supports and sheet metal screws.

  8. Make electrical supply connections in the electrical junction box and connect power supply wires to designated wires using wire nuts (see wiring diagram figure 7 and figure 8). The power cord supplied may be used for installation if local codes and regulations permit. If not permitted, power supply wiring must be minimum of 18-ga. AWG copper and rated for 90° Centigrade installed in a metal cable or conduit. Power connections should be made by a qualified installer to comply with NFPA Standard No. 70 and all local codes and regulations.

NOTE:  Do NOT break off jumper for low voltage.

 

Fig. 7  Model 1500 Wiring Diagram

Fig. 8 Model 2500 Wiring Diagram


Furnace Dimensions

Fig. 9

NORSEMAN™ 1500


 

Fig. 10

NORSEMAN™ 2500


Chimney Connections

DRAFT
Chimneys perform two functions.

  1. As a means of exhausting smoke and flue gases which are the result of fuel combustion.

  2. The chimney provides “draft” which allows oxygen to be continuously introduced into the appliance, so that proper combustion is possible.

NOTE: your furnace does NOT create draft.

Draft is a function of the chimney. A minimum of 0.05 w.c.,( measured in water column) is required for proper drafting to prevent back-puffing, smoke spillage, and to maximize performance. (Gauges to measure chimney draft are readily available at furnace shops and are economical to purchase or rent.)

As of April 1, 1987 all coal stoves should be installed using a factory built chimney that meets the “Type HT” requirement of UL 103 (when using a factory built chimney).

IMPORTANT INSTALLATION POINTS

  1. Size the chimney flue to the furnace pipe. (6" outlet pipe = 6" chimney flue.)

  2. Avoid using elbows except as necessary. Elbows reduce draft, no more than two should be used in any chimney run.

  3. Make sure all horizontal runs of connector pipe have a minimum outward rise of 1/4" per horizontal foot. This allows any condensation or creosote buildup to run back into the firebox.

Manufactured Chimney
REFER TO CHIMNEY AND CHIMNEY CONNECTOR MAKER'S INSTRUCTIONS FOR INSTALLATION AND USE.

Carefully follow chimney manufacturer’s instructions. Use only a listed chimney. If your chimney starts at the ceiling (see figure 13 and figure 14) you will need enough 6” round black connector pipe to reach the ceiling. The top of the chimney must be at least three (3) feet above the roof and be at least two (2) feet higher than any point of the roof within ten (10) feet (figure 13). Use only 6” diameter listed chimney UL 103 HT. Chimney made to this listing is High Temperature rated to 2100 degrees Fahrenheit. Use chimney from only one manufacturer. Never mix brands. Carefully follow the chimney manufacturer’s stated requirements and clearances. Use the chimney manufacturer’s attic guards, roof supports, flashing and fire stops when passing through a ceiling. Use a listed thimble when passing through a combustible wall. Do not use makeshift compromises during installation. Never use a single-wall connection pipe as a chimney! NEVER USE A SINGLE-WALL CONNECTION PIPE AS A CHIMNEY!

When using a pre-existing chimney, have it’s condition and installation inspected before using. Make sure that the chimney meets all of the UL rating requirements listed above. Be aware that not all manufactured chimney is of the UL 103 HT type.

NOTE: It is recommended that you contact a licensed heating and cooling contractor (consult your local yellow pages) for chimney installation.

Manufactured chimney with the proper required UL listing is available from most home centers, hardware stores, and HVAC supply stores.

If you have access to the internet, you may wish to view chimney manufacturers’ information on-line. See, www.duravent.com, www.selkirkinc.com, or www.mtlfab.com.

Masonry Chimney

Before using an existing masonry chimney, clean the chimney, inspect the flue liner and make any repairs needed to be sure it is safe to use. Make repairs before attaching the furnace. The connector furnace pipe and fittings you will need to connect directly to a masonry chimney are shown in figure 11 and figure 12.

If the connector furnace pipe must go through a combustible wall before entering the masonry chimney, consult a qualified mason or chimney dealer. The installation must conform to local building and fire codes and latest edition of NFPA 211.

Do not connect this furnace into the same
chimney flue as the fireplace, gas appliance, or a flue connected with any other furnace.
The chimney used for a furnace must not be used to ventilate the cellar or basement. If there is a cleanout opening in the base of the chimney, close it tightly.

If you have any questions regarding venting your furnace, contact the manufacturer or contact the National Fire Protection Association (NFPA) and request a copy of the latest editions of NFPA Standard 211 and NFPA Standard 908. Their address is:

Battery March Park, Quincy, MA 02269.

 

  Fig. 11    Masonry Chimney Connection
Masonry Chimney Connection

Fig. 12   Masonry Chimney Connection

Fig. 13  Chimney Construction through Roof

 

Connector Pipe Installation

NOTE: Connector pipe is NOT INCLUDED.
To purchase pipe, visit your local hardware, home or building center. See Locating Furnace for additional specifications.

 Fig. 14   Furnace pipe / Flue Connections:

CORRECT WRONG WRONG

Stove / Flue Installation


  1. The crimped end of the connector pipe fits inside the furnace flue collar. Install additional pipe and elbow with the crimped end towards the furnace. This will allow any condensation in the flue to run back into the firebox.
  2. Horizontal pipe runs must slope upwards towards the chimney at least 1/4” per foot of horizontal run.
  3. You must have at least 18 inches of clearance between any horizontal piping and the ceiling.
  4. Connector pipe cannot extend into the chimney flue (see figure 14).
  5. Secure pipe/elbow sections with three (3) sheet metal screws at each joint to make the piping rigid.
  6. It is recommended that no more than two (2) 90° bends be used in the stovepipe installation. The use of more than two 90° bends may decrease the amount of draw and possibly cause smoke spillage. Where possible, use only corrugated (nonadjustable) elbows. These are much more airtight.
  7. The chimney connector must not pass through an attic or roof space, closet, or any concealed space, or floor, ceiling, wall or combustible construction. See chimney connections. A UL 103 HT Listed chimney must be used from the first penetration of ceiling or wall to the chimney cap.
  8. The chimney connector may include a section for a barometric draft regulator between the furnace and the chimney (see figure 2, figure 11 and figure 13). The optional barometric draft regulator must be installed in the same room (same pressure zone) as the furnace.
  9. Install the optional barometric draft regulator strictly in accordance with the instructions that are provided with the barometric draft regulator.
CAUTION:
NEVER USE SINGLE WALL CONNECTOR PIPE AS A CHIMNEY - A HOUSE FIRE COULD RESULT.

Barometric Draft Regulator Setting

  1. Drill a hole in the chimney connector within 18" of the flue collar below the barometric draft regulator just large enough for the tube of the manometer.

  2. Build a fire after all chimney connections have been made.

  3. Use a manometer to measure the draft in the flue.

  4. Adjust the Barometric Draft Regulator to obtain a draft of 0.05" - 0.06" W.C. under stable fire conditions.

  5. After all adjustments have been made, seal the hole made for the manometer tube with furnace cement.


Operating Instructions

CAUTION: HOUSE FIRE HAZARDS

• Gases emitted from freshly added fuel must be burned or they will
cause creosote to accumulate in the chimney. Never smother a fire when adding fresh fuel.
 
• Never use manufactured coal "bricks" made of coal dust and way-type binder.
 
• Over firing may cause a house fire. If a unit or chimney connector glows, you are over firing.
 
• Build fires only on integral grate included with the furnace.

 

OPERATING SAFETY PRECAUTIONS

1. Never over fire this furnace by building excessively hot fires as a house/building fire may result.

2.  Do NOT operate with feed or ash doors open. Over firing may result.

3. Never build extremely large fires in this type of furnace as damage to the furnace or smoke leakage may result.

4. HOT while in operation. Keep
children, clothing, and furniture away. Contact may cause skin burns. Do NOT touch the furnace after firing until it has cooled.

5. Provide make up air into the room for proper combustion.

 

WARNING: Explosion Hazard

• Never use chemicals, gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar flammable liquids to start or “freshen-up” a fire in the furnace.
 
• Keep all flammable liquids, especially gasoline, out of the vicinity of the Furnace — whether in use or in storage.
 
• Inspect and clean flue pipe every 90 days. Replace immediately if flue pipe is rusting or leaking smoke into the room.
 
• Do not operate furnace with a draft exceeding 0.06" W.C. (water column).

FUEL(S)

This furnace is designed to burn wood or coal fuel.

Coal Fuel
Low ash content (2% to 6%) coal is recommended. Purchase “washed” coal in chestnut, egg, furnace, or nut-sizes (1-3/4 to 4 inch diameter) for residential furnaces. Any of the specialty packaged fireplace coals can also be used. (Do not use wax-type coal “bricks”).

NOTICE: For best results use solid, bituminous coal. Never use manufactured coal "bricks" made of coal dust with wax-type binder. Do NOT burn garbage or flammable fluids. Store coal in dry, well ventilated area.

Wood Fuel
Hardwood, 18" to 26" should be split and air dried (seasoned) for 6 months to provide proper burning without excessive creosote buildup.

Lighting

NOTE: On first use build three (3) small fires to "season" cast iron parts and prevent cracking. Allow furnace to cool between firings.

  1. Set the thermostat on "HIGH" and open draft damper to provide maximum draft.
  2. Open the feed door and place paper and kindling on the grate for starting the fire.
  3. Light fire, close and secure the feed door.
  4. Add wood or about 15 pounds of coal after fire is burning briskly. Use care not to smother the kindling fire when adding coal.
  5. Set the thermostat to maintain desired temperature. “MEDIUM” setting is normally satisfactory. Set higher or lower for your personal comfort level.

Adding Fuel

When starting fires, add small amounts of fuel each hour or so instead of piling large quantities of fuel every 3 to 5 hours. As you become more familiar with the operation of your furnace, it is possible to add fuel to burn for longer periods of time (between 8 to 10 hours), but doing so carelessly will promote incomplete combustion and considerable sooting, along with a very dirty, inefficient fire.

  1. Set thermostat to “HIGH” before opening the feed door.
  2. Never smother the fire when adding fuel (especially coal). Incomplete combustion of fresh coal will cause creosote accumulation and a mild smoky explosion will occur:
    – Add fresh kindling if the bed of coals has cooled.
    -- Add up to 20 lbs. of coal or wood to a convenient level. Never add fuel above the top of the firebrick.
    – Stir the coals and watch the fire. Be sure new fuel is burning before you close the doors and turn the thermostat down.
  3. At least once every 12 hours of operation crank the roller grate system to dump 'clinkers' and ash into the ash pan. A couple of gentle “cranks”, is all that is required. Stop cranking when you observe a few red coals falling into the ash pan. Excessive cranking can expose the grates to very high heat and warp or damage the grates.
  4. Empty ash pan regularly. Do not allow ashes to pile up to the grate. If ashes build up to the grate, it can warp and burnout will occur. If allowed to overfill, ashes may spill when removing the pan.
  5. Properly dispose of hot ashes (see Safety Instructions, item #10.)

Coal Burning Tips

The size of coal fuel is critical - too large and it won’t burn well, too small and it will smother the fire creating excessive smoke and gases. Purchase Bituminous coal “nuggets” that are 1-3/4” to 4” diameter and that have been “cleaned” to remove rocks and other minerals.

Bituminous coal is recommended for ease of use but produces a greater amount of volatile gases so it is important to build and refresh coal fires properly. Extra maintenance will also be required to remove accumulated
soot on heating surfaces and pipes.

All fires should be initially started using wood kindling. Hardwood is best as it creates a hotter bed of coals that is necessary to ignite the coal.

Once a hot bed of wood coals has been established an initial layer of coal may be placed in the firebox. Due to the high amount of volatile gas produced by coal, the initial flames will be long and of an orange or yellow color accompanied by quite a bit of smoke. As the gas is burned off the flames will become shorter, the color will change and less smoke will be produced.

Once the fire is well established, add coal to the center of the firebox in a conical arrangement. The highest
part of the fuel should be in the center of the fire box. This allows the heat to drive off the volatile gases and the turbulence created causes a more efficient burn.

Remember to allow enough secondary air to enter the fire box and keep the stove pipe damper open to properly burn off the volatile gases. You will have to experiment with your particular setup (fire construction,
fuel load, spin draft control, damper and automatic settings) as no two arrangements of furnace/chimney are the same.

When refueling a coal fire, use a poker to break up any crust that may have formed being careful not to mix the coal which may increase the chance of forming “clinkers.”

Banking a Coal Fire

A fire should be banked for extended operation without tending, such as overnight. This is accomplished by heaping the fuel along the sides and back of the fire box so that the fire gradually burns through the fuel. This reduces the intensity of the fire without letting it go out.

Use the same procedures as in refueling but without shaking the grates. The layer of ash will help to reduce the intensity of the fire. After loading the fuel in this manner, let the fire establish itself for about 30 minutes then close the damper and adjust the automatic control to a point so that the house does not get too cold. Make sure you leave yourself enough time to bank the fire before leaving or retiring so you can make the necessary adjustments after the fire has become well established.

Reviving a Fire

To revive a fire that has almost gone out, increase the draft through the grates by opening the ash door and stove pipe damper and closing the door spin draft control(s). Place a thin layer of new coal over the entire fire but DO NOT SHAKE the fire grates. Doing so may cause the live coals to drop through the grates. Once the fresh layer of coal has ignited you may shake the grates (slightly) and refuel as usual.

CAUTION: DO NOT SMOTHER A FIRE WHEN ADDING COAL. GASES DRIVEN OFF FROM FRESH COAL MUST BE BURNED OR THEY MAY ACCUMULATE AND EXPLODE. WHENEVER REFUELING, OPEN THE PIPE DAMPER AND TURN THE THERMOSTAT DAMPER TO HIGH BEFORE OPENING THE DOOR TO ALLOW ANY ACCUMULATED GASES TO BE BURNED OFF.


Blower Limit Control Settings
 

The temperature in the plenum of the warm air furnace
at which the blower turns on or off, is controlled by the blower limit control settings. Indicators (see figure 7 and figure 8) in the control may be adjusted through their entire range of settings to achieve the desired warm air output (see figure 15).

Move both pointers towards the right (counter clockwise) – this increases the temperature setting at which the blower will turn on and off. Move both pointers towards the left (clockwise) – this decreases the on/off temperature setting. Increasing the distance between the pointers increases the time the blower will run on each warm air cycle.

Fig. 15 - Blower Limit Control Settings

Power Failure Instructions

Operation during power loss:
Do not expect to keep home at normal temperatures.
1. Remove filter if provided.
2. Reduce fire to a low burn.
3. Set bimetal thermostat on LOW setting and set spin draft on ash door to a minimum of one turn open.
4. Do not load fuel above bottom of feed door.

Blower Fan and Motor Care

Oil blower motor(s) twice a year. Add five drops of light weight (SAE 20) oil to each oiler tube. If the blower and fan accumulate moderate to heavy dust, vacuum, wipe and/or blow dust from motor housing and fan.


Chimney Maintenance

CHIMNEY DRAFT

Do not expect the furnace to draw. Draft is a function of the chimney, NOT the furnace. Smoke spillage into the house or excessive buildup of condensation or soot in the chimney are warnings that the chimney is NOT functioning properly. Correct the problem before using the furnace. Following are some possible causes for improper draft.

  1. The connector stovepipe may be pushed into the chimney too far, stopping the draft (figure 14).

  2. If the chimney is operating too cool, water will condense in the chimney and run back into the furnace. Soot formation will be rapid and may block the chimney. Operate the furnace at a high enough fire level to keep the chimney warm preventing this condensation.

  3. If the fire burns well but sometimes smokes or burns slowly, it may be caused by the chimney top being lower than another part of the house or a nearby tree. The wind blowing over a house or tree, falls on top of the chimney like water over a dam, beating down the smoke. The top of the chimney should be at least three (3) feet above the roof and be at least two (2) feet higher than any point of the roof within ten (10) feet.

NOTE: A draft reading of 0.05 W. C. (Water Column) is suggested for proper burning of this furnace.

CREOSOTE -  Formation and Removal

When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. If ignited, this creosote creates an extremely hot fire which may ignite surrounding materials resulting in a building fire.

The chimney connector and chimney should be inspected at least twice a month during the heating season to determine if a creosote buildup has occurred.

If creosote has accumulated, it should be removed. Failure to remove creosote may result in ignition and may cause a house/building fire. Creosote may be removed using a chimney brush or other commonly available materials from your local hardware retailer.

Chimney fires burn very hot. If the chimney connector should glow red, immediately call the fire department, then reduce the fire by closing the inlet air control and pour a large quantity of coarse salt, baking soda, or cool ashes on top of the fire in the firebox.
 

CAUTION: A chimney fire may cause ignition of wall studs or rafters which were assumed to be a safe distance from the chimney. If a chimney fire has occurred, have your chimney inspected by a qualified person before using again.

End of Season Maintenance

Remove all accumulated ash from inside fire box and ash drawer compartment. Ash will absorb moisture and can cause corrosion.


Installation Arrangements

Your NORSEMAN™ Warm Air Furnace can be installed as a supplemental add-on unit (see figure 16) or as a central heating system (see figure 17). The following illustrations depict the various installation configurations which may be used to install your NORSEMAN™ Warm Air Furnace. Always have a qualified heating equipment professional install your furnace.

Fig. 16   Parallel Add-On Installation

Fig.  17   Central Installation

Fig. 18   Add-on Heat Pipe Installation


 

NOTE:
To prevent damage from overheating, Backdraft Dampers must be installed no closer than 18 inches to the top surface of the furnace.

Fig.  19  Add-on Plenum Collector Box

Fig.  20   Add-on Optional Plenum Collector


 

NOTE:
To prevent damage from overheating, Backdraft Dampers must be installed no closer than 18 inches to the top surface of the furnace.

Fig.  21   Add-on Plenum Backdraft Flapper

Fig.  22   Add-on Angled Plenum


 

NOTE:
To prevent damage from overheating, Backdraft Dampers must be installed no closer than 18 inches to the top surface of the furnace.

Fig.  23   Central Furnace Installation

Order Norseman™ 1500 online

Order Norseman™ 2500 online

Order replacement parts for the Norseman™  2500 Furnace

Order replacement parts for the Norseman™  1500 Furnace

Cold Air Return Enclosures for the Norseman™  Add-on Furnaces

DK-50 Draft Induction Kit 


This Vogelzang heating appliance is safe when installed properly and will provide you with years of service. However, always exercise good judgment when you are using this furnace. You are dealing with FIRE! Fire is inherently dangerous and must be treated with respect. Stay warm and in good health!

Respectfully yours,

Steve Vogelzang

Proprietor

Company Testimony:

"For God so loved the world that he gave his only begotten Son, that whoever believes in Him shall not perish but have eternal life"

John 3:16

MADE IN CHINA

go backReplacement parts page

Cast Iron Wood and Coal Stoves Plate Steel Wood Stoves Circulator Wood and Coal Stoves
EPA CERTIFIED WOOD STOVES Add-on Furnaces Barrel Stove Kits Heat Reclaimers
Customer Comments Dealer Information Policies F. A. Q. ALL Stoves Home

Vogelzang International Corporation