|
NORSEMAN™ WOOD SOLID WARM AIR
FURNACE
Model 2500 and
1500 Owners Manual (Save this manual for future
reference. Go to PDF format for
printing.)
|
READ ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING
THIS FURNACE.
Failure to follow instructions
may result in property damage, bodily injury, or even death. |
|
|
|
NOTE: Installation MUST be
completed by a qualified
Heating Equipment Installer! |
May NOT be installed in
mobile homes, manufactured homes, trailers or tents.
(No Exceptions) |
|
|
|
This furnace meets
U.S. Test Standard: |
UL 391 |
SAFETY INSTRUCTIONS
|
|
| Safety Notice: If this
furnace is NOT properly installed, a house/building fire
may result. For your safety, contact local building or fire officials about
permits, restrictions, and installation requirements for your area.
|
READ ALL INSTRUCTIONS CAREFULLY.
Refer to instruction panels, caution and warning plates on furnace for
additional information.
- This furnace is designed for INDOOR
INSTALLATION ONLY.
-
DO NOT attempt to retrofit this unit with any type
of water coil or water jacket.
-
The installation of this furnace must comply with
your local building code rulings. Please observe the clearances to combustibles
(see
figure 1,
figure 2, figure 3). Do not place
furniture or other objects within the clearance area.
-
Verify that the furnace is properly installed before
firing for the first time. Obtain the services of a professional licensed
installer familiar with all aspects of safe and correct installation. DO NOT use
temporary or makeshift compromises during installation.
-
DO NOT store wood, flammable liquids or other
combustible materials too close to the unit. Refer to the certification label on
back of unit and reference
clearance instructions in this manual.
-
Do not install this furnace in a mobile home,
manufactured home, tent or trailer – NO EXCEPTIONS! (HUD Federal Standard: 24
CFR Ch.XX)
-
If any parts are missing or defective, please notify
the manufacturer or dealer immediately. DO NOT OPERATE A STOVE THAT IS MISSING
ANY PARTS.
-
Always connect this furnace to a chimney and vent to
the outside. Never vent to another room or inside a building. DO NOT CONNECT
THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
-
DO NOT CONNECT to
an aluminum Type B gas vent. This is not safe. Use approved masonry or a
UL 103 HT Listed Residential Type and Building Heating Appliance
Chimney. Use a 6" diameter chimney or larger, that is high enough
to provide required draft (see specifics in
installation instructions.)
-
Inspect flue pipes, pipe joints, and flue pipe seals
regularly to ensure that smoke and flue gases are not drawn into, and circulated
by the air circulation system.
-
Cleaning of this furnace, is especially important at
the end of the heating season. Accumulated ash attracts moisture and may cause
corrosion during the summer months.
- Be sure that your chimney is safely
constructed and in good repair. Have the chimney inspected by the fire
department or a qualified inspector. Your insurance company may be able to
recommend a qualified inspector.
- Creosote or soot may build up in the chimney
connector and/or chimney and cause a house, building or chimney fire.
Inspect the chimney connector and chimney twice monthly during the
heating season and clean if necessary. (See Chimney
Maintenance).
- To prevent injury, do not allow anyone to
use this furnace who is unfamiliar with the correct operation of the furnace.
- Do not operate furnace while under the influence of drugs or alcohol.
- Ashes should not be allowed to
accumulate higher than the ash pan. Dispose of
ashes in a metal container with a tight fitting lid.
Keep the closed container on a noncombustible
floor or on the ground, well away from all combustible materials. Keep the ashes in the closed
container until all cinders have thoroughly
cooled. The ashes may be buried in the ground or
picked up by a refuse collector.
- Build several small fires on first use. This
will help to “season” the cast iron parts and avoid cracking. Allow furnace
to cool between firings.
- The special paints used on your furnace may
give off some smoke and an odor while they
are curing during the first 12 to 15 fires.
Additional smoke and odor may be emitted from the light oils used in
construction of the fire box. This should disappear after a short period of
time and not occur again. Persons with lung conditions or owners of
susceptible domestic pets (such as birds) should take prudent precautions.
Open windows
and doors as needed to clear smoke and/or odor. Paint discoloration will
occur if the furnace
is over fired.
- This furnace has a painted surface which is durable but it will not stand rough handling
or abuse. When installing your furnace, use care in handling. Clean with soap and warm
water when furnace is not hot. Do not use any acids or scouring soap, as these solvents wear and dull
the finish.
- While furnace is in operation, all persons,
especially young children, should be alerted to the hazards from high
surface temperatures and should be kept away to avoid burns or clothing
ignition.
- If small children will be in the same room
as the furnace during operation, provide a sturdy barrier to keep them at a
safe distance from the stove. NEVER LEAVE SMALL CHILDREN UNSUPERVISED
when they are in the same room as the stove.
- Keep furnace area clear and free from all combustible materials, gasoline, and other
flammable vapors and liquids.
-
To prevent burns, always wear protective
clothing, leather hearth gloves and eye
protection, while tending the fire.
-
While in operation, keep the feed door, ash door, and
cabinet door closed and secured at all times except while tending the fire.
-
Do not overfire the furnace. Overfiring will
occur if the feed door or ash door is left open during operation. Such actions
can result in very
dangerous operating conditions.
-
For further information on using your
furnace safely, obtain a copy of the National Fire Protection Association (NFPA) publication, "Using Coal and Wood
Furnaces Safely" NFPA No. HS-10-1978. The address of the NFPA is: Battery March Park, Quincy, MA 02269.
| NOTE: INSTALLATION SHOULD
BE COMPLETED BY A PROFESSIONAL, LICENSED HEATING AND COOLING CONTRACTOR
ONLY. |
FURNACE DESCRIPTION & INSTALLATION OPTIONS
Your NORSEMAN™ Solid Fuel Warm Air Furnace is designed to
provide supplemental or central heating for your home. This solid fuel furnace
may be installed in conjunction with a central furnace that is in proper
operating condition and meets all national and/or local building codes, safety
standards, required controls and has been installed in accordance with
appropriate standards of the National Fire Protection Association and in
accordance with the clearances specified on the furnace nameplate.
Installation of NORSEMAN™ Furnaces must be accomplished by a
qualified heating contractor (one who is engaged in, and is responsible for, or
is thoroughly familiar with the installation and operation of gas, oil, and
solid fuel burning heating appliances, who is experienced in such work and
familiar with all the requirements of the authority having jurisdiction.) The
installation shall be in strict accordance with the manufacturer’s installation
instructions furnished with the solid fuel furnace.
The chimney connector of the furnace is to be installed to
provide clearances to combustible materials not less than specified in the
individual classifications and marked on the furnace. The chimney must be
suitable for use with residential type or building heating appliances which burn
solid fuel.
The furnace is designed to operate in either parallel air
flow arrangement with a central furnace or as a stand alone central furnace.
(See connection option diagrams, figures 17 – 23 below)
Central Furnace Installation
As a central furnace, the unit functions independently of any
other heating system. The blower(s) will come on when the plenum temperature
reaches the setting on the blower control.
Parallel Installation
When the NORSEMAN™ Warm Air Furnace is installed in parallel with an existing
central heating furnace, it is designed to turn on the central unit blower
whenever the Warm Air Furnace blower turns on. The NORSEMAN™ blower will only
come on when the temperature in the plenum has reached the setting on the blower
control. This insures there will be sufficient warm air in the system to provide
for efficient operation. When the central system thermostat calls for heat, the
central system will operate by igniting the burner and turning on the blower. It
is possible that both systems will operate simultaneously. For the most
efficient use of your
NORSEMAN™ Warm Air Furnace, it is recommended that it be
fired as much as possible in order to reduce the demand on the central heating
system. An optional forced draft kit (Model DK-50) is available that operates
from a wall thermostat. When the temperature falls below the setting on the wall
thermostat, the forced draft will come on.
The warm air supply outlet of the NORSEMAN™ Furnace MUST
NOT BE CONNECTED TO THE COLD AIR RETURN of the central heating furnace
because of the possibility of overheating components of the central furnace and
causing it to operate other than it was designed.
Operating external static pressure and air temperature rise of existing
furnace must be within ratings marked on the central furnace nameplate. Test
operation of central furnace after installation of supplementary furnace.
Locating Furnace
NOTICE: Installation of this furnace must
be done by a qualified heating equipment installer.
|
CAUTION:
FURNACE UNITS ARE HEAVY.
UNITS WEIGH APPROXIMATELY 450-550 LBS. MAKE SURE YOU HAVE PROPER
EQUIPMENT OR SUFFICIENT MANPOWER TO PREVENT INJURY WHEN DELIVERING AND
LOCATING FURNACE UNITS. |
| CAUTION:
DO NOT OPERATE THIS APPLIANCE WITH CRACKED OR MISSING FIREBRICKS. |
- The furnace must be placed on solid
concrete or masonry floor.
NOTE: To reduce weight during installation remove parts from inside the
firebox. Additional weight reductions can be obtained by removing the
fire brick. Make
note of position so they are returned to the same positions.
- The furnace should be located in the same room as the
central heating system, as close as possible but no closer than 6˝ to
the central system. (See figures 16 – 23 below)
- Observe the clearances to combustible
materials (see figure 1,
figure 2 and figure 3).
- The furnace must have its own flue.
Do not connect this unit to a chimney flue serving other appliances.
- Install furnace pipe, elbows, and
thimble as required, utilizing either a recently cleaned and inspected
6" masonry chimney or a 6" i.d. listed UL 103 HT chimney. NOTE: A
barometric draft regulator may be necessary if the chimney draft is
found to be excessive.
|
- Use 6" round black furnace pipe, not
galvanized furnace pipe. Secure pipe sections with three (3) sheet metal
screws in each furnace pipe and/or elbow joint to firmly hold the pipe
sections together.
- Recheck clearances from the furnace,
connector furnace pipe, and corner clearances
using the illustrations in figures 1 – 3 and your local building codes
or fire protection ordinances.
NOTE: A studded wall faced with brick or stone should be
considered a combustible surface.
- DO NOT INSTALL THIS FURNACE IN A
MOBILE HOME, MANUFACTURED HOME, TENT OR TRAILER. NO EXCEPTIONS! (HUD
Federal Standard: 24 CFR Ch.XX)
- The clearances provided are minimum
dimensions determined by the manufacturer’s testing facility in
accordance with U.S. Test Standard
UL 391. Installation of this furnace must comply with the latest
edition of NFPA 211 for reduced clearances and/or your local building
code rulings (use whichever minimum dimensions are LARGEST).
|
|
Minimum Clearances to Combustible Surfaces
Front: 48 in. Side: 16 in. Back: 26 in.
Chimney Connectors: 18 in.
Plenum to wall-studs, joists or finished wall or ceiling: 2 in. |
Fig.
1 - TOP VIEW
Minimum Clearances from Combustible Surfaces
 |
Fig.
2 - SIDE VIEW
Minimum Clearances
from Combustible Surfaces
 |
Fig. 3 -
Minimum Plenum Clearances from Combustible Surfaces

Tools & Materials Required for Assembly and Installation
| TOOLS
REQUIRED |
MATERIALS
REQUIRED |
Safety Glasses
Gloves
Pencil
6 foot Tape Measure
Tin Snips
Sabre Saw
Drill1/8" diameter Drill Bit (for sheet metal screws)
Screwdrivers (Phillips & Slotted)
6mm Socket with Driver
10mm Socket with Driver
10mm open end box wrench
7/16" box wrench |
NOTE: The following items are NOT
included with your furnace
Chimney Connection:
6" black steel (24 ga. minimum) straight
furnace pipe, elbow, Collar and Thimble
(as required)
6" Barometric Draft Regulator (optional)
8" Round Butterfly Anti-Backdraft Damper
(2 required - for parallel installation only)
Plenum & Duct Work (as required)
Chimney: Existing 6" Lined Masonry Chimney or
6" Inside Diameter listed Type HT chimney.
1/2" Sheet Metal Screws
Electrical Wiring: 18 ga. AWG copper
with 90° C min.
1/2" Conduit and Connectors
Furnace Cement (manufacturer recommends
Rutland Code 78 or equivalent) |
ASSEMBLY INSTRUCTIONS
Refer to diagram and parts lists:
1500 | 2500
Your NORSEMAN™ Warm Air Furnace
requires the following items to be assembled or installed by the furnace
installer:
Feed Door Pull Handle / Thermostat Assembly
Feed Door Locking Handle
Blower(s) and Blower Control
Electrical Connections
- Remove all parts from inside the furnace
and inspect for damage, including the firebrick as some breakage could
occur during shipment. Do not operate furnace with broken or missing
fire box bricks. Replace damaged bricks before operating furnace.
- Assemble the feed door handle a shown in
figure 4. Install thermostat assembly and cover as
shown.
- Align thermostat control know with flat
on thermostat control shaft and press onto shaft (see figure 4).
- Attach feed door locking handle (see
figure 5) with screw and nuts provided. NOTE: Slotted
holes are for adjustment of handle. Adjust handle until pressure is
required to lock feed door.
- Install Blower / Limit Control on rear of
furnace cabinet using three (3) sheet metal screws (see figure
6).
- Remove blower(s) from carton(s). Attach
the flexible conduit / wire assembly to the blower(s) before mounting.
- Remove
junction box cover and take out the mounting hardware package. Position clip nuts to furnace housing around blower
opening as shown in figure
6. [On Model #2500, install
the right (when facing rear of furnace) blower first.] Install the blower(s) with
gasket using 1/4-20 x 3/4" bolts.
- Secure the 4-inch square electrical
junction box to the black bracket on the rear of the stove using two (2)
sheet metal screws.
- Wire blower according to the wiring
diagram shown (see figure 7 and figure 8).
On model 2500, wire right side blower first (see
figure 7). Replace junction box cover when complete.
- Connect operation of shaker grates with
grate handle before loading fuel in furnace.
|
Fig.
4 Door / Handle / Thermostat Assembly

Fig. 5
Feed Door Handle Assembly

Fig. 6 Blower Assembly

Model 1500 has 1 blower centered on cabinet.
Model 2500 had 2 blowers - install right first.
|
Furnace Installation
NOTE: Installation must be made by a qualified
heating equipment installer (one who is engaged in, and is responsible for,
or is thoroughly familiar with the installation and operation of gas, oil, and
solid fuel burning heating appliances, who is experienced in such work and
familiar with all the building requirements and/or fire codes of the authority
having local jurisdiction.)
This is a furnace, not a stove. Heated air must
be directed away from the furnace or it will not operate properly.
-
The installation is to be completed in
accordance with National Fire Protection Association (NFPA) installation
standards No. 89M, 90B, 211, 70 (National Electrical Code) and Uniform
Mechanical Code 913, 6-4 in states where applicable (where code offers making
flue pipe connections into an existing chimney with other fuel burning
appliances).
-
Wood /coal burning appliances need air for
combustion and circulation to the house. Provision must be made to provide
make up air so as not to starve the central heating system of combustion air.
Have the local regulating authority determine that make up air supply is
adequate. Reference NFPA standards No. 30 & 54, Code for Installation of Gas
and Oil Equipment.
-
Have the local regulating authority or
qualified expert inspect all chimneys and installations for adequate venting
and for compliance with standard local codes and regulations regarding
installation of wood/coal burning appliances. (Also see
Pipe Installation)
-
Position the furnace according to clearances
(see
figure 1,
figure 2, figure 3) and to maintain
chimney connections as short as possible. Avoid unnecessary turns and
installation of devices that would create excessive resistance to the flow of
flue gases.
-
Make flue pipe connections to the chimney with
24-gauge pipe and elbows (not included with furnace) maintaining proper
clearances. Seal the flue pipe in the chimney with furnace cement. (Chimney
connections must be securely supported and joints fastened with sheet metal
screws or rivets.)
-
For parallel installations,
install (two) 8" anti-backdraft butterfly dampers (Vogelzang Model AD-8,
not included with the furnace) in the heat (duct) pipes a minimum of 18
inches above the furnace plenum. Anti-backdraft butterfly dampers may be
obtained where you purchased your appliance or from a local HVAC
distributor.
-
Install 8˝ diameter 26-gauge
heat (duct) pipe and connectors (not included with furnace) to make
connection to the plenum of the central heating system. The heat pipe,
plenum, and connections must be constructed of metal with a minimum
temperature rating of 250° F. If central air conditioning is installed in
the plenum, install heat pipe above the air conditioning unit. Secure the
heat pipe connection with supports and sheet metal screws.
-
Make electrical supply connections in the
electrical junction box and connect power supply wires to designated wires
using wire nuts (see wiring diagram figure 7 and
figure 8). The power cord supplied may be used for
installation if local codes and regulations permit. If not permitted, power
supply wiring must be minimum of 18-ga. AWG copper and rated for 90°
Centigrade installed in a metal cable or conduit. Power connections should be
made by a qualified installer to comply with NFPA Standard No. 70 and all
local codes and regulations.
| NOTE:
Do NOT break off jumper for low voltage. |
|
Fig. 7 Model 1500 Wiring Diagram
 |
Fig. 8 Model 2500 Wiring Diagram
 |
| Furnace Dimensions
Fig. 9
NORSEMAN™ 1500
|
 |
 |
 |
Chimney Connections
DRAFT
Chimneys perform two functions.
-
As a means of exhausting smoke and
flue gases which are the result of fuel combustion.
-
The chimney provides “draft” which
allows oxygen to be continuously introduced into the appliance, so that proper
combustion is possible.
NOTE: your furnace does
NOT
create draft.
Draft is a function of the chimney. A minimum of 0.05 w.c.,(
measured in water column) is required for proper drafting to prevent
back-puffing, smoke spillage, and to maximize performance. (Gauges to measure
chimney draft are readily available at furnace shops and are
economical to purchase or rent.)
As of April 1, 1987 all coal stoves
should be installed using a factory built chimney that meets the “Type HT”
requirement of UL 103 (when using a factory built chimney).
IMPORTANT INSTALLATION POINTS
-
Size the chimney flue to the
furnace pipe.
(6" outlet pipe = 6" chimney flue.)
-
Avoid using elbows except as necessary. Elbows
reduce draft, no more than two should be used in any chimney run.
-
Make sure all horizontal runs of
connector pipe have a minimum outward rise of 1/4" per
horizontal foot. This allows any condensation or
creosote buildup to run back into the firebox.
Manufactured Chimney
REFER TO CHIMNEY AND CHIMNEY CONNECTOR MAKER'S INSTRUCTIONS FOR
INSTALLATION AND USE.
Carefully follow chimney
manufacturer’s instructions. Use only a listed chimney. If your chimney
starts at the ceiling (see figure 13 and figure 14)
you will need enough 6” round black connector pipe to reach the ceiling. The
top of the chimney must be at least three (3) feet above the roof and be at
least two (2) feet higher than any point of the roof within ten (10) feet
(figure 13). Use only 6” diameter listed chimney UL 103 HT. Chimney made to
this listing is High Temperature rated to 2100 degrees Fahrenheit. Use
chimney from only one manufacturer. Never mix brands. Carefully follow the
chimney manufacturer’s stated requirements and clearances. Use the chimney
manufacturer’s attic guards, roof supports, flashing and fire stops when
passing through a ceiling. Use a listed thimble when passing through a
combustible wall. Do not use makeshift compromises during installation.
Never use a single-wall connection pipe as a chimney! NEVER USE A
SINGLE-WALL CONNECTION PIPE AS A CHIMNEY!
|
When using a pre-existing chimney, have it’s
condition and installation inspected before using. Make sure that the chimney
meets all of the UL
rating requirements listed above. Be aware that not all manufactured chimney is
of the UL
103 HT type.
NOTE: It is recommended that you contact a licensed heating and
cooling contractor (consult your local yellow pages) for chimney installation.
Manufactured chimney with the proper required
UL listing is available from most home centers, hardware stores, and HVA C
supply stores.
If you have access to the internet, you may
wish to view chimney manufacturers’ information on-line. See,
www.duravent.com,
www.selkirkinc.com, or
www.mtlfab.com.
Masonry Chimney
Before using an existing masonry chimney, clean the chimney, inspect the flue
liner and make any repairs needed to be sure it is safe to use. Make repairs
before attaching the furnace. The connector furnace pipe and fittings you will
need to connect directly to a masonry chimney are shown in
figure 11
and figure 12.
If the connector furnace pipe must go through a combustible wall before
entering the masonry chimney, consult a qualified mason or chimney dealer. The
installation must conform to local building and fire codes and latest edition of
NFPA 211.
Do not connect this furnace into the same chimney flue as the fireplace, gas appliance, or a flue connected with any other
furnace. The chimney used for a furnace must not be used to ventilate the cellar
or basement. If there is a cleanout opening in the base of the chimney, close it
tightly.
If you have any questions regarding venting your furnace, contact the
manufacturer or contact the National Fire Protection Association (NFPA) and
request a copy of the latest editions of NFPA Standard 211 and NFPA Standard
908. Their address is:
Battery March Park, Quincy, MA 02269.
|
Fig. 11
Masonry Chimney Connection
 Fig. 12
Masonry Chimney Connection
 Fig.
13
Chimney Construction through
Roof

|
Connector Pipe Installation
NOTE: Connector pipe is NOT
INCLUDED.
To purchase pipe, visit your local hardware, home or building center.
See
Locating Furnace for additional specifications.
|
Fig. 14
Furnace pipe / Flue Connections:

- The crimped end of the connector
pipe fits inside the furnace flue collar. Install additional pipe
and elbow with the crimped end towards the furnace. This will allow
any condensation in the flue to run back into the firebox.
- Horizontal pipe runs must slope upwards
towards the chimney at least 1/4” per foot of horizontal run.
- You must have at least 18 inches of
clearance between any horizontal piping and the ceiling.
- Connector pipe cannot extend into the chimney
flue (see figure 14).
- Secure pipe/elbow sections with three
(3) sheet metal screws at each joint to make the piping rigid.
- It is recommended that no more than two
(2) 90° bends be used in the stovepipe installation. The use of more
than two 90° bends may decrease the amount of draw and possibly cause
smoke spillage. Where possible, use only corrugated (nonadjustable)
elbows. These are much more airtight.
- The chimney connector must not pass
through an attic or roof space, closet, or any concealed space, or
floor, ceiling, wall or combustible construction. See
chimney connections. A UL 103 HT Listed chimney must be used
from the first penetration of ceiling or wall to the chimney cap.
- The chimney connector may include a
section for a barometric draft regulator between the furnace and the
chimney (see figure 2, figure 11 and
figure 13). The optional barometric draft regulator must be
installed in the same room (same pressure zone) as the furnace.
- Install the optional barometric draft regulator
strictly in accordance with the instructions that are provided with the
barometric draft regulator.
CAUTION:
NEVER USE SINGLE WALL CONNECTOR PIPE AS A CHIMNEY - A HOUSE FIRE COULD
RESULT. |
|
Barometric Draft Regulator Setting
-
Drill a hole in the chimney connector within
18" of the flue collar below the barometric draft regulator just large enough
for the tube of the manometer.
-
Build a fire after all chimney connections
have been made.
-
Use a manometer to measure the draft in the
flue.
-
Adjust the Barometric Draft Regulator to
obtain a draft of 0.05" - 0.06" W.C. under stable fire conditions.
-
After all adjustments have been made, seal the
hole made for the manometer tube with furnace cement.
Operating Instructions
|
CAUTION: HOUSE FIRE HAZARDS
• Gases emitted from freshly added fuel must
be burned or they will cause creosote to accumulate in the chimney. Never smother a fire when adding
fresh fuel.
• Never use manufactured coal "bricks" made of coal
dust and way-type binder.
• Over firing may cause a house fire. If a unit or chimney connector glows, you
are over firing.
• Build fires only on integral grate included with the furnace. |
|
OPERATING SAFETY PRECAUTIONS
1. Never over fire this furnace
by building excessively hot fires as a
house/building fire may result.
2. Do NOT operate with feed
or ash doors open. Over firing may result.
3. Never build extremely large fires in this type of furnace
as damage to the furnace or smoke leakage may result.
4. HOT while in operation. Keep
children, clothing, and furniture away. Contact may cause skin burns.
Do NOT touch the furnace after firing until it has cooled.
5. Provide make up air into the room for proper combustion. |
|
WARNING: Explosion Hazard
• Never use chemicals, gasoline, gasoline-type
lantern fuel, kerosene, charcoal lighter fluid, or similar flammable liquids to
start or “freshen-up” a fire in the furnace.
• Keep all flammable liquids, especially gasoline, out of the vicinity of the
Furnace — whether in use or in storage.
• Inspect and clean flue pipe every 90 days. Replace immediately if flue pipe is
rusting or leaking smoke into the room.
• Do not operate furnace with a draft exceeding 0.06" W.C. (water column). |
|
|
FUEL(S)
This furnace is designed to burn wood or coal fuel.
Coal Fuel
Low ash content (2% to 6%) coal
is recommended. Purchase “washed” coal in chestnut, egg,
furnace, or nut-sizes (1-3/4 to 4 inch diameter) for residential
furnaces. Any of the specialty packaged fireplace coals can also
be used. (Do not use wax-type coal “bricks”).
|
NOTICE: For best results
use solid, bituminous coal. Never use manufactured coal "bricks" made of
coal dust with wax-type binder. Do NOT burn garbage or flammable fluids.
Store coal in dry, well ventilated area. |
Wood Fuel Hardwood, 18" to 26" should be split and air dried (seasoned) for 6 months to
provide proper burning without excessive creosote buildup.
Lighting
NOTE: On first use build three
(3) small fires to "season" cast iron parts and prevent
cracking. Allow furnace to cool between firings.
- Set the thermostat on "HIGH"
and open draft damper to provide
maximum draft.
- Open the feed door and place
paper and kindling on the grate for starting the fire.
- Light fire, close and secure
the feed door.
- Add wood or about 15 pounds of
coal after fire is
burning briskly. Use care not to smother the kindling fire
when adding coal.
- Set the thermostat to maintain
desired temperature. “MEDIUM” setting is normally satisfactory. Set higher or lower for your
personal comfort level.
Adding Fuel
When starting fires, add small
amounts of fuel each hour or so instead of piling large
quantities of fuel every 3 to 5 hours. As you become more
familiar with the operation of your furnace, it is possible to
add fuel to burn for longer periods of time (between 8 to 10
hours), but doing so carelessly will promote incomplete
combustion and considerable sooting, along with a very dirty,
inefficient fire.
- Set thermostat to “HIGH” before opening the feed door.
- Never smother the fire when adding fuel
(especially coal). Incomplete combustion of fresh coal will cause creosote accumulation and a
mild smoky explosion will occur:
– Add fresh kindling if the bed of coals has cooled. -- Add up to 20 lbs. of coal or wood to a convenient
level. Never add fuel above the top of the firebrick. – Stir the coals and watch the fire. Be sure new fuel is burning before you
close the doors and turn the thermostat down.
- At least once every 12 hours of operation
crank the roller grate system to dump 'clinkers' and ash into the ash
pan. A couple of gentle “cranks”, is all that is required. Stop cranking when
you observe a few red coals falling into the ash pan.
Excessive cranking can expose the grates to very high heat
and warp or damage the grates.
- Empty ash pan regularly. Do not allow ashes to
pile up to the grate. If ashes build up to the grate, it can warp and burnout
will occur.
If allowed to overfill, ashes may spill when
removing the pan.
- Properly dispose of hot ashes (see
Safety Instructions, item #10.)
|
Coal Burning Tips
The size of coal fuel is
critical - too large and it won’t burn well, too small and it will smother
the fire creating excessive smoke and gases. Purchase Bituminous coal
“nuggets” that are 1-3/4” to 4” diameter and that have been “cleaned” to
remove rocks and other minerals.
Bituminous coal is recommended
for ease of use but produces a greater amount of volatile gases so it is
important to build and refresh coal fires properly. Extra maintenance will
also be required to remove accumulated
soot on heating surfaces and pipes.
All fires should be initially
started using wood kindling. Hardwood is best as it creates a hotter bed of
coals that is necessary to ignite the coal.
Once a hot bed of wood coals has
been established an initial layer of coal may be placed in the firebox. Due
to the high amount of volatile gas produced by coal, the initial flames will
be long and of an orange or yellow color accompanied by quite a bit of
smoke. As the gas is burned off the flames will become shorter, the color
will change and less smoke will be produced.
Once the fire is well
established, add coal to the center of the firebox in a conical arrangement.
The highest
part of the fuel should be in the center of the fire box. This allows the
heat to drive off the volatile gases and the turbulence created causes a
more efficient burn.
Remember to allow enough
secondary air to enter the fire box and keep the stove pipe damper open to
properly burn off the volatile gases. You will have to experiment with your
particular setup (fire construction,
fuel load, spin draft control, damper and automatic settings) as no two
arrangements of furnace/chimney are the same.
When refueling a coal fire, use
a poker to break up any crust that may have formed being careful not to mix
the coal which may increase the chance of forming “clinkers.”
Banking a Coal Fire
A fire should be banked for
extended operation without tending, such as overnight. This is accomplished
by heaping the fuel along the sides and back of the fire box so that the
fire gradually burns through the fuel. This reduces the intensity of the
fire without letting it go out.
Use the same procedures as in
refueling but without shaking the grates. The layer of ash will help to
reduce the intensity of the fire. After loading the fuel in this manner, let
the fire establish itself for about 30 minutes then close the damper and
adjust the automatic control to a point so that the house does not get too
cold. Make sure you leave yourself enough time to bank the fire before
leaving or retiring so you can make the necessary adjustments after the fire
has become well established.
Reviving a Fire
To revive a fire that has almost
gone out, increase the draft through the grates by opening the ash door and
stove pipe damper and closing the door spin draft control(s). Place a thin
layer of new coal over the entire fire but DO NOT SHAKE the fire grates.
Doing so may cause the live coals to drop through the grates. Once the fresh
layer of coal has ignited you may shake the grates (slightly) and refuel as
usual.
|
CAUTION: DO NOT SMOTHER A FIRE WHEN ADDING COAL.
GASES DRIVEN OFF FROM FRESH COAL MUST BE BURNED OR
THEY MAY ACCUMULATE AND EXPLODE. WHENEVER REFUELING,
OPEN THE PIPE DAMPER AND TURN THE THERMOSTAT DAMPER
TO HIGH BEFORE OPENING THE DOOR TO ALLOW ANY
ACCUMULATED GASES TO BE BURNED OFF. |
Blower Limit Control Settings
|
The temperature in the
plenum of the warm air furnace
at which the blower turns on or off, is controlled by the blower
limit control settings. Indicators (see figure 7
and figure 8) in the control may be adjusted
through their entire range of settings to achieve the desired warm
air output (see figure 15).
Move both pointers towards the right
(counter clockwise) – this increases the temperature setting at
which the blower will turn on and off. Move both pointers towards
the left (clockwise) – this decreases the on/off temperature
setting. Increasing the distance between the pointers increases the
time the blower will run on each warm air cycle. |
Fig.
15 - Blower Limit Control Settings
 |
Power Failure Instructions
Operation during power loss:
Do not expect to keep home at normal temperatures. 1. Remove filter if provided.
2. Reduce fire to a low burn. 3. Set bimetal thermostat on LOW setting
and set spin draft on ash door to a minimum of one turn open. 4. Do not load fuel above bottom of feed door.
Blower Fan and Motor Care
Oil blower motor(s) twice a year. Add five drops
of light weight (SAE 20) oil to each oiler tube. If the blower and fan
accumulate moderate to heavy dust, vacuum, wipe and/or blow dust from motor
housing and fan.
Chimney
Maintenance
CHIMNEY DRAFT
Do not expect the furnace to draw. Draft is a
function of the chimney, NOT the furnace. Smoke spillage into the house or
excessive buildup of condensation or soot in the chimney are warnings that the
chimney is NOT functioning properly. Correct the problem before using the
furnace. Following are some possible causes for improper draft.
-
The connector stovepipe may be
pushed into the chimney too far, stopping the draft (figure 14).
-
If the chimney is operating too
cool, water will condense in the chimney and run back into the furnace. Soot
formation will be rapid and may block the chimney. Operate the furnace at a high
enough fire level to keep the chimney warm preventing this condensation.
-
If the fire burns well but sometimes
smokes or burns slowly, it may be caused by the chimney top being lower than
another part of the house or a nearby tree. The wind blowing over a house or
tree, falls on top of the chimney like water over a dam, beating down the smoke.
The top of the chimney should be at least three (3) feet above the roof and be
at least two (2) feet higher than any point of the roof within ten (10) feet.
| NOTE: A draft
reading of 0.05 W. C. (Water Column) is suggested for proper
burning of this furnace.
|
CREOSOTE -
Formation and Removal When
wood is burned slowly, it produces tar and other organic vapors which combine
with expelled moisture to form creosote. The creosote vapors condense in the
relatively cool chimney flue of a slow-burning fire. As a result, creosote
residue accumulates on the flue lining. If ignited, this creosote creates an
extremely hot fire which may ignite surrounding materials resulting in a
building fire. The chimney
connector and chimney should be inspected at least twice a month during
the heating season to determine if a creosote buildup has occurred.
If creosote has accumulated, it should be removed. Failure to remove creosote
may result in ignition and may cause a house/building fire. Creosote may be
removed using a chimney brush or other commonly available materials from your
local hardware retailer. Chimney fires burn very hot. If the chimney connector should glow red,
immediately call the fire department, then reduce the fire by closing the inlet
air control and pour a large quantity of coarse salt, baking soda, or cool ashes
on top of the fire in the firebox.
| |