|
SENTRY COAL™ STOVE
Model VG810CL Owners Manual
(Save this manual for future reference.
Go to PDF format for
printing.)
| READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING THE
INSTALLATION OR OPERATING THE STOVE. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY
INJURY, OR EVEN DEATH.
|
|
|
|
May NOT be installed in
mobile homes, manufactured homes, trailers or tents.
(No Exceptions) |
|
|
|
This stove meets
U.S. Test Standard:
UL 1482-1996
|
|
|
|
SAFETY INSTRUCTIONS
| Safety Notice: If this stove is not properly installed, a house/building fire
may result. For your safety, contact local building or fire officials about
permits, restrictions, and installation requirements for your area.
|
Read All Instructions carefully.
- The installation of this stove must comply with your local building code
rulings.
Please observe the clearances to combustibles (see figure 3, figure
4 & figure 5). Do not place furniture or other
objects within the clearance area.
-
Verify that the stove is properly installed before
firing the stove for the first time. After reading these instructions, if you
have any doubt about your ability to complete your installation properly, you
must obtain the services of a professional licensed installer familiar with all
aspects of safe and correct installation. DO NOT use temporary or makeshift
compromises during installation.
-
DO NOT store coal, kindling, flammable liquids or
other combustible materials too close to the unit. Refer to certification label
on back of unit (see figure 3, figure
4 & figure 5).
-
DO NOT install this stove in a mobile home,
manufactured home, trailer or tent. (NO EXCEPTIONS! per HUD Federal Standard CFR
Ch. XXX).
-
If any parts are missing or defective, please notify
the dealer or manufacturer immediately. DO NOT OPERATE A STOVE THAT IS MISSING
ANY PARTS!.
-
Do not tamper with combustion air control beyond
normal adjustment capacities.
-
Always connect this stove to a chimney
and vent to the outside. Never vent to another room or inside a building. DO NOT
CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
-
DO NOT CONNECT a coal burning stove to
an aluminum Type B gas vent. This is not safe. Use approved masonry or a
UL 103 HT (U.S.) Listed Residential Type and Building Heating Appliance
Chimney. Use a 6" diameter chimney or larger, that is high enough
to give a good draft (see specifics in chimney installation
instructions.)
-
Be sure that your chimney is safely constructed
and in good repair. Have the chimney inspected by the fire department or a qualified inspector. Your insurance
company may be able to recommend a qualified inspector.
-
Creosote or soot may build up in the
chimney connector and chimney and cause a house/building fire. Inspect the chimney connector
and chimney twice monthly during the heating season and clean if necessary (see Chimney
maintenance).
-
In the event of a chimney fire, turn the air control
to closed position, leave the building and CALL THE FIRE DEPARTMENT
IMMEDIATELY! Have a clearly understood plan on how to handle a chimney fire
by contacting your local fire authority for information on proper procedures in
the event of a chimney fire.
-
To prevent injury, do not allow anyone to
use this stove who is unfamiliar with the correct operation of the stove.
-
Do not operate stove while under the influence of drugs or alcohol.
-
Ashes should not be allowed to accumulate higher
than the ash pan. Dispose of ashes in a metal container with a tight fitting
lid. Keep the closed container on a noncombustible floor or on the ground, well
away from all combustible materials. Keep the ashes in the closed container
until all cinders have thoroughly cooled. The ashes may be buried in the ground
or picked up by a refuse collector.
-
The special paints used on your stove may give off
some smoke and an odor while they are curing during the first 12 to 15 fires.
Additional smoke and odor may be emitted from the light oils used in
construction of the fire box. This should disappear after a short period of time
and not occur again. Persons with lung conditions or owners of susceptible
domestic pets (such as birds) should take prudent precautions. Open windows and
doors as needed to clear smoke and/or odor. Paint discoloration will occur if
the stove is overfired.
-
This stove has a painted surface which is durable
but it will not stand rough handling or abuse. When installing your stove, use
care in handling. Clean with soap and warm water when stove is NOT hot. Do not
use any acids or scouring soap, as these wear and dull the finish.
-
The walls of the firebox may become slightly
distorted after a period of use. A slight distortion will not affect the
operation of the stove.
-
While stove is in operation, all persons, especially
young children should be alerted to the hazards from high surface temperatures.
Keep away from a hot stove to avoid burns or clothing ignition.
-
If small children will be in the same room as the
stove during operation, provide a sturdy barrier to keep them at a save distance
from the stove. NEVER LEAVE SMALL CHILDREN UNSUPERVISED when they are in
the same room as the stove.
-
Keep stove area clear and free from all combustible
materials, gasoline, and other flammable vapors and liquids.
-
To prevent burns always wear protective clothing,
leather hearth gloves and eye protection, while tending the fire.
-
While in operation, keep the feed door, ash door,
and cabinet door closed at all times except while tending the fire.
-
Do not overfire the stove. Overfiring will happen if
the feed door or ash door is left open during operation. Such actions can result
in very dangerous operating conditions.
-
All power cords and electrical appliances and/or
assemblies must be kept outside of the clearance dimensions shown in this manual
for combustible materials.
-
For further information on using your
stove safely, obtain a copy of the National Fire Protection Association (NFPA) publication, "Using Coal and Wood Stoves Safely"
NFPA No. HS-10-1978. The address of the NFPA is:
Battery March Park, Quincy, MA 02269.
| NOTE: A PROFESSIONAL,
LICENSED HEATING AND COOLING CONTRACTOR MUST BE CONSULTED IF YOU HAVE
QUESTIONS REGARDING THE INSTALLATION OF THIS SOLID FUEL BURNING
APPLIANCE. |
ASSEMBLY INSTRUCTIONS
NOTICE: Vogelzang International Corp. grants no
warranty, stated or implied, for the installation or maintenance of your wood
stove and assumes no responsibility of any incidental or consequential damages.
| TOOLS
REQUIRED |
MATERIALS
REQUIRED |
|
Pencil
6 foot Folding Rule or Tape Measure
Tin Snips
Drill: Hand or Electric
1/8" diameter Drill Bit
(sheet metal screws)
1/4" diameter Drill Bit (damper installation)
Screwdrivers
(blade and Phillips types)
6mm Nut Driver or Ratchet
with 6mm Socket
Safety Glasses
Gloves
|
(NOTE: The following items are NOT
included with your stove) |
|
Chimney Connection: 6" black steel (24
gauge minimum) straight stove pipe or elbow (as required)
1/2" Sheet Metal Screws
Chimney: Existing 6" Lined Masonry Chimney or 6"
Inside Diameter listed Type HT chimney.
Flooring Protection: 42" x 60" as specified
(see Locating Stove)
Furnace Cement (manufacturer recommends
Rutland Code 78 or equivalent) |
| CAUTION: Stove is heavy. Make sure you have adequate help and use proper
lifting techniques whenever moving stove.
|
|
|
Refer to diagram and parts list.
|
|
|
- Uncrate the stove and remove cardboard
packing and protective poly bag.
(Save cardboard for further assembly.)
- Remove legs, upper and lower heat shields, damper
and hardware pack from inside firebox.
- Place flattened carton behind stove and carefully
turn stove onto its back.
- Join the upper and lower heat shields with four
(4) self-tapping screws (see figure 1).
|
Fig. 1
Leg and Heat Shield Assembly

|
| WARNING: Metal panels fastened
between legs acts as a heat deflectors. These panels must be in place for
safe operation. |
- Place both legs upside down and attach
the heat shield assembly (from step 4) between the legs. Align
the holes in the heat shield assembly with those in the
mounting flange of the leg assemblies and secure with four (4)
self-tapping screws.
- Attach leg / heat shield assembly to the
base of the stove using self-tapping screws provided (see figure
1).
- Carefully lift stove to upright
position.
- Locate the door knob and machine screw in the
hardware pack. Open the cabinet door by reaching under the cabinet
frame and pulling the door open.
- Install the door knob onto the outside of the
door. Install the machine screw through the latch bracket, door, and
into the knob. Tighten securely (see figure 2).
|
Fig. 2
Cabinet Door Knob Assembly
 |
Locating Stove
- The stove must be
placed on solid concrete, solid masonry, or when installed on a
combustible floor, on a listed floor protector, use a minimum 3/8"
noncombustible floor protector with an "R" factor of 0.8, such as Hy-C or
Imperior
Model UL 4260BK or equivalent. (NOTE: to calculate R-values of
equivalent alternative materials, click here.) The base must extend at least 16"
beyond the side with the access door, 8" to the sides of fuel
opening, and must extend
under the stove pipe if it is elbowed towards a wall. (See figure
3
& figure 4 and
consult local building codes and fire protection ordinances.)
Fig. 3
TOP VIEW: Minimum Clearance Dimensions from Combustible Surfaces:
- The stove must have its own flue. Do
not connect this unit to a chimney flue serving other appliances.
- After observing the clearances to combustible
materials (see figure 4
& figure 5), locate your floor protector accordingly
(figure 3) and carefully place the stove in your selected location.
Install stove pipe, elbows, and thimble as required, utilizing either a recently cleaned
and inspected 6" masonry chimney or a 6" i.d.
listed chimney (see pipe installation).
- Use 6" round black stove pipe, not
galvanized stove pipe. Secure pipe sections with three
(3) sheet metal screws in each stove pipe and/or elbow joint to firmly hold the pipe sections
together. Do Not connect this stove to any air distribution or
duct system.
- Recheck clearances from the stove, connector stove pipe, and corner clearances using the illustrations
(figure 3, figure 4 & figure
5) and
your local building codes or fire protection ordinances.
NOTE: A wall faced with drywall, brick or
stone must be considered a combustible surface.
- DO NOT INSTALL THIS STOVE IN A
MOBILE
HOME, TRAILER OR TENT – NO EXCEPTIONS!
(HUD Federal Standard: 24 CFR Ch. XX)
|
|
Fig. 4
TOP VIEW: Minimum Corner
Clearances from
Combustible Surfaces

CORNER CLEARANCES
|
- The clearances provided are minimum dimensions
determined by the manufacturer's testing facility. Installation of this stove must comply with the latest
edition of NFPA 211 for reduced clearances and / or your local
building code rulings. Use whichever minimum dimensions are LARGEST.
Failure to follow these minimum clearance requirements may
result in an unsafe installation
and could cause a fire.
- This stove meets U. S. Test Standard: UL
1482-1996.
| CAUTION: Keep furnishings and other
combustible materials away from the stove.
|
| NOTE: Before firing stove, slide firebricks towards the rear so no gaps remain between
bricks.
|
|
Fig. 5a
Front View Fig.
5b Side View

Minimum
Clearances from
Combustible Surfaces
|
D-6 Draft Damper
A Draft Damper included with the stove
must be installed in the first straight section of pipe exiting the stove
before the stove pipe is connected and the wood stove is used.
Fig. 6 Draft Damper Installation
 |
- Drill two (2) 1/4" holes centered on either side of the
pipe section 6" from the top end of the pipe (see figure
6).
- Remove the handle from the damper then slide the damper into
the pipe.
- Align the damper with the holes drilled in step 1 and insert
the handle through the holes and the damper.
NOTE: This damper is necessary for the proper operation of
the stove and to meet EPA emissions requirements for heating
appliances.
It MUST be installed before use.
(NO EXCEPTIONS) |
Pipe Installation
- The crimped end of the stovepipe fits inside the
stove collar. Install additional pipe and elbow with the crimped end
towards the stove. This will allow any condensation in the flue to run
back into the firebox.
- Horizontal pipe runs must slope upwards towards the chimney at least 1/4" per foot
of horizontal run.
- You must have at least 18 inches of
clearance between any horizontal piping and the ceiling.
- The pipe cannot extend into the chimney
flue (figure 7).
- Secure pipe/elbow sections with three (3)
sheet metal screws at each joint to make the
piping rigid.
- It is recommended that no more than two
(2) 90° bends be used in the stovepipe installation. The use of more than two 90° bends may
decrease the amount of draw and possibly cause smoke spillage. Where possible, use only
corrugated (nonadjustable) elbows. These are much more airtight.
- The chimney connector must not pass
through an attic or roof space, closet, or any concealed space, or
floor, ceiling, wall or combustible construction. (See chimney connector systems and
clearances.). A UL 103 HT Listed chimney must be used
from the first penetration of ceiling or wall to the chimney cap.
Never use single wall connector pipe as a chimney – a house fire
could result!
| NOTE: Stove pipe is NOT INCLUDED.
To purchase pipe, visit your local hardware, home or building center. See
Locating Stove for
additional specifications.
|
Fig. 7
Stovepipe / Flue Connections:

|
Chimney Connections
The stove must be connected to either a masonry
or manufactured metal chimney built and tested to the specifications listed on
the previous pages.
Chimneys perform two functions.
- As a means of exhausting smoke and
flue gases which are the result of fuel combustion.
- The chimney provides “draft” which allows
oxygen to be continuously introduced into the appliance, so that proper
combustion is possible. This stove relies on natural draft to operate.
|
|
Fig. 8
Masonry Chimney Connection
|
NOTICE: Always provide a
source of fresh air into the room where the stove is located. Failure to do so
may result in air starvation of other fuel burning appliances and the possible
development of hazardous conditions, fire or death.
Your stove itself does not create
draft. Draft is provided by the chimney. To achieve proper draft your chimney
must meet the three minimum height requirements (see figure 9, figure 10 & figure
11). A minimum of 0.05 w.c. (measured in water column) is required for
proper drafting to prevent back puffing, smoke spillage, and to maximize
performance. (Gauges to measure draft are readily available at stove stores and
are economical to rent or purchase.)
Factors such as wind, barometric
pressure, trees, terrain and chimney temperature can have an adverse effect on
the draft. The manufacturer cannot be held responsible for external factors
leading to less than optimal drafting.
Should you have a problem with
inadequate draft, you should contact a licensed heating and cooling contractor
for assistance in solving the problem.
IMPORTANT Installation Points
-
Size the chimney flue to the stove pipe.
This stove requires a 6” diameter flue.
-
Never connect this unit to
a chimney serving another appliance.
-
The chimney must meet all
minimum height requirements.
-
Never use a chimney to
ventilate a cellar or basement.
-
Contact your local
building authority for approved methods of installation and any
necessary permits and/or inspections.
|
Masonry Chimney
Before using an existing masonry
chimney, clean the chimney, inspect the flue liner and
make any repairs needed to be sure it is safe to use.
Make repairs before attaching the stove. The
connector stove pipe and fittings you will need to connect
directly to a masonry chimney are shown in
figure 8.
If the connector stove pipe must go through
a combustible wall before entering the masonry
chimney, consult a qualified mason or chimney
dealer. The installation must conform to local building
and fire codes and latest edition of NFPA 211.
If there is a cleanout opening in the
base of the chimney, close it tightly.
|
|
Fig. 9
Chimney Construction Through Attic Space:
 |
Manufactured Chimney
REFER TO CHIMNEY AND CHIMNEY
CONNECTOR MAKER’S INSTRUCTIONS FOR INSTALLATION AND USE.
Use only 6” diameter listed chimney UL 103 HT.
Chimney made to this listing is High Temperature rated to 2100 degrees
Fahrenheit. Use chimney from only one manufacturer. Never mix brands. Carefully follow chimney manufacturer's
stated requirements and clearances. Use the chimney manufacturer’s attic guards,
roof supports, flashing and fire stops when passing through a ceiling. Use a
listed thimble when passing through a combustible wall. Do not use makeshift
compromises during installation. Never use a single-wall connection pipe
as a chimney!
When using a pre-existing chimney,
have it’s condition and installation inspected before using. Make sure that the
chimney meets all of the UL rating requirements listed above. Be aware that not
all manufactured chimney is of the UL 103 HT type.
NOTE: It is recommended that you contact a licensed
heating and cooling contractor (consult your local yellow pages) for chimney
installation. Manufactured
chimney with the proper required UL listing is available from most home centers,
hardware stores, and HVAC supply stores. If you have access to the internet, you
may wish to view chimney manufacturers’ information on-line. See,
www.duravent.com,
www.selkirkinc.com, or
www.mtlfab.com.
|
Fig. 10
Chimney Construction Through Roof:
Fig. 11
Chimney Connection to Firebox
Through Masonry Wall:
|
|
Venting to Existing Fireplace
In some instances, people desire to convert
an existing fireplace for stove use. Usually, safe
connection to an existing masonry chimney
requires more work than using a prefabricated chimney. The existing fireplace must be closed and
sealed at the damper with high-temperature caulk,
ceramic wool, or furnace cement.
Prior to installation,
clean and inspect the existing flue and smoke shelf.
Installation should be designed so the
system can be dismantled for periodic cleaning and inspection. Before conversion, make sure the
existing chimney is structurally sound, the
chimney incorporates a flue liner and make sure it is in good condition. (A flue liner consists of
clay tile that protects the brickwork of a chimney. If
a chimney does not have a liner, or it is damaged, have it relined by a professional.
Do Not use a chimney that is unlined or
damaged!)
If you have any question regarding the condition of the
chimney, consult a qualified licensed contractor, qualified engineer, competent mason,
certified Chimney Sweep, or a knowledgeable inspector. Consult your insurance company if you cannot
find a qualified expert.
| CAUTION: Not all fireplaces are suitable for conversion to a wood stove.
Check with a qualified expert.
|
Many prefabricated fireplaces are of the
"zero-clearance fireplace" category. These consist of multi-layered metal construction. They are designed
with enough insulation and/or air cooling on the
base, back and sides so they can be safely installed
in direct contact with combustible floors and
walls.
Although many prefabricated fireplaces carry
endorsements from nationally recognized organizations for use as fireplaces, they have not been
tested for connection to wood stove heaters.
Connecting a stove to such a device will void the manufacturer's warranty.
|
Steel-lined fireplaces are constructed with
1/4" firebox liner, an air chamber in connection
with 8" of masonry. These can be safely used with
wood burning stoves. They contain all the
essential components of a fireplace, firebox,
damper, throat, smoke shelf, and smoke chamber. Many look identical to masonry fireplaces and should
be checked carefully before connecting a stove to them.
Venting a stove directly into a fireplace does
not meet code and should not be attempted. (This
constitutes connection to another appliance - the
fireplace.) Combustion products will be deposited
and build up in the firebox or fireplace. The stove
warranty will be void with such an installation. Do
not create a hazard in your home by connecting in
this manner.
Fireplace Installation
Directly connecting the stovepipe into the
existing masonry chimney (see figure 12 "Type A"
fireplace conversion) of the fireplace is the only
approved method of installation. This is a
complicated and involved process and to insure safety should only by done by a qualified installer.
-
An entry hole must be cut through the
masonry and tile liner with minimal damage to the
liner. At least 8" of liner must remain below the entry position. When locating the stove and stovepipe, all minimum clearances must be
observed from combustible surfaces including mantels, combustible
trimwork, ceilings
and walls. Positioning the center of the stove
pipe entry into the chimney 24" below the
ceiling should insure proper clearance for a 6" stovepipe.
-
Install a metal or fire clay (5/8" minimum thickness) thimble. Make sure the thimble is flush with the inner surface of the chimney liner
and does not protrude into the flue (see figure 7).
-
Secure the thimble with refractory mortar.
The thimble should be surrounded by 8" of solid unit
masonry brickwork or 24" of stone.
-
Install the stovepipe into the thimble as far
as possible without extending past the flue lining (see figure 7 &
figure 8).
-
A small airspace (about 1/2") should
remain between the stovepipe and thimble to allow
for expansion of the pipe. Seal this airspace with high-temperature caulking or ceramic wool.
-
Secure and seal the damper in the closed position using high-temp caulking, ceramic wool, or furnace cement. Also check to see
if the chimney has a cleanout. If it does, make
sure it is closed and sealed as well. A leaky
cleanout will greatly reduce draft efficiency.
|
Fig. 12
Fireplace
Conversion:
 |
|
If you have any questions regarding venting your stove, contact the manufacturer or
contact the National Fire Protection Association (NFPA) and request a copy of the latest editions of
NFPA Standard 211 and NFPA Standard 908.
Their address is:
Battery March Park, Quincy, MA 02269.
|
Operating Instructions
|
CAUTION: HOUSE FIRE HAZARDS
-
Gases emitted from freshly added
coal must be burned or they will accumulate and explode. Never smother a
fire when adding fresh coal.
-
Never use manufactured coal
"bricks" made of coal dust and wax-type binder.
-
Overfiring may cause a house fire.
If a unit or chimney connector glows, you are overfiring.
-
Build fires only on integral
grate included with the stove.
-
Do not operate the heater with
the minimum fire air shutter completely closed.
|
|
WARNING: EXPLOSION HAZARD
-
Never use chemicals, gasoline,
gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar
flammable liquids to start or
"freshen-up" a fire in the stove.
-
Keep all flammable liquids,
especially gasoline, out of the vicinity
of the stove, whether in use or in storage.
-
The use of wood in this stove
except for initial ignition purposes, is a violation of federal law.
|
|
OPERATING SAFETY PRECAUTIONS
1. Never overfire this stove by
building excessively hot fires as a house/building fire may result. If stove or
stovepipe begins to glow or turn red, you are overfiring the stove.
2. Never build extremely large
fires in this type of stove as damage to the stove or smoke leakage may result.
3. HOT while in operation.
Keep children, clothing, and Furniture away. Contact may cause
skin burns. Do not touch the stove
after firing until it has cooled.
4. Provide air into the room for
proper combustion.
5. Inspect stovepipe every
90 days.
Replace immediately if stovepipe is rusting or leaking smoke into the room.
|
|
|
This stove is designed to burn
COAL FUEL ONLY.
Chestnut, egg, stove, or nut-size coal for
residential furnaces, or any of the specialty packaged fireplace coals (not
wax-type coal "bricks") can be used. Low ash content (2% - 6%) coal is recommended.
| NOTICE: For best
results use solid, bituminous coal. Never use manufactured coal
"bricks" made of coal dust with wax-type binder. Do not burn
garbage or flammable fluids. Store coal in dry, well ventilated area. See
recommendations for using Anthracite Coal.
|
Lighting
- Set the thermostat on "HIGH"
and open pipe draft damper to provide
maximum draft.
- Using the separable handle, open the
feed door and place paper and kindling on the grate for
starting the fire.
- Light fire, close and secure the feed
door.
- Add about 15 pounds of coal after fire
is burning briskly. Use
care not to smother the kindling fire when adding coal.
- Set the thermostat to maintain desired
temperature. "Medium" setting is normally
satisfactory. Set higher or lower for your personal comfort
level.
Adding Fuel
When possible, add small amounts of coal each hour or so
instead of piling large quantities of fuel every 3 to 5 hours. As you become
more familiar with the operation of your stove, it is possible to add coal to
burn for longer periods of time (between 8 to 10 hours), but doing so carelessly
will promote incomplete combustion and considerable sooting, along with a very
dirty, inefficient fire.
- Set thermostat to "HIGH" and
open pipe draft damper before opening the feed door.
- Never smother the fire when adding
coal. Incomplete combustion of fresh coal will cause gas
accumulation and a mild smoky explosion will occur:
- Add fresh kindling if the bed of
coals has cooled
- Add up to 20 pounds of coal. Never
add coal above the top of the firebrick.
- Stir the coal and watch the fire.
Be sure the new coal is burning before you close the
doors and turn the thermostat down.
- At least once every 12 hours
of operation, crank the roller grate system to dump
'clinkers' and ash into the ash pan.
- Empty the ash pan regularly. Do not
allow ashes to pile up to the grate.
If ashes build up to the grate, it can warp and burnout will
occur. If allowed to overfill, ashes may spill when removing
the pan.
- Properly dispose of hot ashes (see Safety
Instructions, item #10.)
|
Minimum Fire
The rate of burning at the
"LOW" thermostat setting can be further controlled by adjusting
the draft damper door located behind the cabinet on the front of the firebox
(see
figure 14).
-
Partially close the shutter to make
the fuel burn longer.
-
Open the shutter, exposing a larger
opening, to reduce the formation of soot (see Chimney
Draft).
-
Do Not operate the heater with the
minimum fire shutter completely closed (see figures 5a and
5b).
Minimum Fire Air Shutter
The thermostat
control was calibrated at the factory and is not adjustable. The operation
of the heater may require a change in calibration of the minimum fire
air shutter. Calibration adjustments should be made at room temperature.
The minimum fire air shutter is mounted on the door of the thermostat
draft damper mounted behind the front screen on the lower front of the
firebox (see figure 14). After stove has cooled, the
cabinet lid may be opened to make adjustments.
CAUTION:
DO NOT OPEN OR CLOSE
TOP WHEN HEATER IS HOT!
- To open, grasp the
cabinet top at front (see figure 13) and lift
all the way up.
- Gently lower the top until the top support
rod latches to hold the top in the "up" position (see
figure
13).
- To close, lift the top until the support rod
is unlatched.
- Pull the support rod forward as you lower the
cabinet top.
Adjusting the Minimum Air Shutter: The minimum
air shutter has an infinite number of settings. Several adjustments
may be necessary for the unit to work most effectively for your
particular installation.
- The minimum air shutter may be adjusted to
the closed position in installations where the draft is
"above normal." Generally, 0.06 w.c. or above would be
considered "above normal".
- In installations where the draft is
"below normal", the minimum air shutter would be
adjusted toward the open position.
|
Fig.
13 Thermostat Adjustment Access

Fig. 14 Minimum Shutter
Adjustment
 |
NOTE: More than one recalibration may be
necessary. At room temperature (72° F) and "LOW" setting, the
draft damper door should be closed.
Recommendations for burning
Anthracite Coal
- When burning coal, it is important to maintain
a clean chimney. Inspect chimney connector and chimney at least
twice monthly during the heating season.
- Keep the grate clear of ash and cinders. Use the shaker
grate to keep the ashes from building up in the firebox.
- DO NOT operate the stove with the ash door, feed
door, or the cabinet door open.
- Before adding coal, it is necessary to have a good hot log
fire burning. After the log fire is burning, add small amounts
of coal until a bed of coals has been built up. Anthracite
Coal burns with a short, blue flame, with the coals having a
glowing, red color.
- Anthracite Coal needs a strong draft to burn efficiently. A
draft reading of 0.05 to 0.06 w.c. (water column) is required
to burn Anthracite.
|
Fig. 15
Feed Door Wheel Adjustment
 |
The draft wheel located on the feed
door (see figure 15) provides a source of secondary air
and should be opened when burning coal. Coal emits volatile gases when
burned and requires a source of secondary air for complete combustion to
occur. The draft wheel may be adjusted to give the best performance
depending on the particular needs of the user.
CHIMNEY DRAFT:
Do not expect the stove to draw. Draft is a function
of the chimney, not the stove. Smoke spillage into the house or
excessive buildup of condensation or soot in the
chimney are warnings that the chimney is NOT
functioning properly. Correct the problem before using the
stove. Following are some possible causes for
improper draft.
-
The connector stovepipe may be pushed
into the chimney too far, stopping the draft.
-
If the chimney temperature is too cool,
water will condense in the chimney and run back into the stove. Soot formation
will be rapid and may block the chimney. Operate the stove at a high
enough fire level to keep the chimney warm preventing this
condensation.
-
If the fire burns well but sometimes
creates excess smoke or burns slowly, it may be caused
by the chimney top being lower than another part
of the house or a nearby tree. The wind blowing
over a house or tree, falls on top of the chimney like
water over a dam, beating down the smoke. The top
of the chimney should be at least three (3) feet
above the roof and be at least two (2) feet higher than
any point of the roof within ten (10) feet.
| NOTE: A draft
reading of 0.05 to 0.06 W. C. (Water Column) is suggested for proper
burning of this stove.
|
Chimney
Maintenance
CREOSOTE -
Formation and Removal:
When coal is burned slowly, it produces tar and other
organic vapors which combine with expelled moisture
to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire.
As a result, creosote residue accumulates on the
flue lining. If ignited, this creosote creates an
extremely hot fire which may ignite surrounding materials resulting in a building fire.
The chimney connector and chimney should
be inspected at least twice a month during the heating season to
determine if a creosote buildup has occurred.
If creosote has accumulated, it should be
removed. Failure to remove creosote may result in ignition and may cause a house/building fire.
Creosote may be removed using a chimney brush or other commonly available materials from your
local hardware retailer.
Chimney fires burn very hot. If the chimney connector should glow red, immediately call the fire
department, then reduce the fire by
closing the inlet air control and pour a large quantity of coarse salt, baking
soda, or cool ashes on top of the fire in the firebox.
| CAUTION: A chimney fire may cause ignition of wall studs or rafters
which were assumed to be a safe distance from the chimney. If a chimney fire
has occurred, have your chimney inspected by a qualified expert before
using again.
|
Floor Protector Material Calculations
This stove has been tested for and must be installed
on a floor protector with the proper Thermal Resistance or R-value as stated in
the installation instructions for Locating Stove, step
1, of this manual. If the floor protector materials listed in the instructions
are not available, materials with an equivalent R-value may be substituted.
Alternate materials may be
rated with C-factor (Thermal Conductance) or k-factor (Thermal Conductivity)
ratings which must be converted to R-value to determine if the alternate
material meets the tested requirements. The following instructions provide the
proper information and formulas for conversion to R-value.To determine if alternate materials are acceptable follow
this sequence.
- Convert material specifications to R-value:
- R-value given — no conversion necessary
- k-factor is given with a required thickness (T) in
inches: R = 1/k x T
- C-factor is given: R = 1/C
- Determine the R-value of proposed alternate floor
protector:
- Use formulas in step 1 above to calculate R-value of
proposed material(s).
- For multiple layers, add R-values of each layer to
determine overall R-value.
- If the overall R-value of the floor protector system is
equal to or greater than the floor protector specifications given, the
alternate is acceptable.
Definitions:
| Thermal conductance(C) = |
BTU
(hr)(ft2)(°F) |
= |
W
(m2)(°K) |
|
|
| Thermal conductivity
(k) = |
(Btu)(inch)
(hr)(ft2)(°F) |
= |
W
(m)(°K) |
= |
Btu
(hr)(ft)(°F) |
| Thermal resistance (R) = |
(ft2)(hr)(°F)
Btu |
= |
(m2)(°K)
W
|
|
|
Example:
The specs of floor protector material should be 3/4-inch
thick material with a k-factor of 0.84.
The proposed alternative material is 4" brick with a C-factor
of 1.25 over 1/8-inch mineral board
with a k-factor of 0.29.
Step 1: Convert specs to R-value.
R = 1/k x T = 1/0.84 x 0.75 = 0.893 System must have a
R-value of 0.893 = Rspecs
Step 2: Calculate R-value of individual components
4" Brick with C-factor = 1.25. R = 1/C = 1/1.25 = 0.80 =
Rbrick
1/8-inch (0.125") mineral board with k-factor = 0.29. R =
1/0.29 x 0.125 = 0.431 = Rmin.brd.
Step 3: Add R-values of components to get total R-value of
system
Rbrick + Rmin.brd = 0.80 + 0.431 = 1.231 = Rsystem
Step 4: Compare Rsystem to Rspecs
Rsystem = 1.231 is larger than Rspecs of 0.893. System R-value exceeds the
required
specifications and therefore is an acceptable alternative.
Order
internal replacement parts for the Sentry Coal™ Stove
Order
external replacement parts for the Sentry Coal™ Stove
Optional
F-1 Heat Circulator Blower
Wood
stove accessories
This Vogelzang heating appliance is safe when installed properly and will provide you with years
of service. However, always exercise good judgment when you are using this stove. You are dealing
with FIRE! Fire is inherently dangerous and must be treated with respect. Stay warm and in good health!
Respectfully yours,
Steve Vogelzang
Proprietor
|
Company Testimony:
"For God so loved the world that he gave his only begotten Son, that
whoever believes in Him shall not perish but have eternal life"
John 3:16
|
MADE IN CHINA

Cast Iron Wood
and Coal Stoves
Plate Steel Wood Stoves
Circulator Wood and Coal Stoves
EPA CERTIFIED WOOD STOVES
Add-on Furnaces
Barrel Stove Kits
Heat Reclaimers
Customer Comments
Dealer Information
Policies
F. A. Q.
ALL Stoves
Home
|